10 realistic exam questions, graded as you go, with the exact rule or statute citation for every answer. Start free, no sign-up.
Timed mock exam
48 questions in 58 minutes, drawn from every topic. No answers shown until the end, then a full score breakdown, your weakest topics and a review of what you missed.
Prices are in US dollars, plus tax where it applies. Stripe, our payment processor, calculates tax at checkout.
All sales are final. If something is really wrong, such as a duplicate charge or a purchase that does not unlock what you bought, write to support@careerexampro.com and we will put it right.
One-time payment. Nothing renews.
You have an exam ticket for this practice test. Start the timed mock exam to use it.
Under EIA-310-D / IEC 60297 rack standards, what is the vertical height of one rack unit (1U), and where should the heaviest storage JBODs or rack-mount UPS units be installed inside a 42U cabinet?
1.75 in (44.45 mm); mount heaviest chassis at the bottom for stability.
2.00 inches (50.80 mm); mount the heaviest chassis at the top to aid natural convection cooling.
1.50 inches (38.10 mm); mount the heaviest chassis in the middle at 20U–24U for ergonomic access.
1.75 inches (44.45 mm); mount the heaviest chassis at the top so overhead cable trays support them.
Show the answer
A. 1.75 in (44.45 mm); mount heaviest chassis at the bottom for stability.
One standard rack unit (1U) equals 1.75 inches (44.45 mm), containing three mounting holes spaced across the rail. Heavy equipment (UPS modules, battery packs, dense storage enclosures) must always be mounted at the bottom of the rack to lower the center of gravity and prevent tip-over hazards when sliding rails out.
A colocation facility has N+1 redundant UPS modules and chillers, but only a single active chilled-water distribution loop and a single electrical switchgear path serving the computer room. Taking the main switchgear offline for preventive maintenance requires shutting down IT racks. What is the highest Uptime Institute Tier level this design satisfies?
Tier II, because it provides redundant capacity components without concurrent maintainability of distribution paths.
Tier III, because N+1 UPS modules and N+1 chillers are sufficient to achieve concurrent maintainability.
Tier IV, because an N+1 capacity layout automatically isolates any planned electrical switching event.
Tier I, because having N+1 redundant capacity components is ignored unless dual utility substations exist.
Show the answer
A. Tier II, because it provides redundant capacity components without concurrent maintainability of distribution paths.
Uptime Institute Tier II adds redundant capacity components (such as N+1 UPS units and chillers) to a single non-redundant distribution path, meaning planned maintenance on the distribution path still forces an IT shutdown. Tier III requires concurrent maintainability across every component and distribution path, while Tier IV adds automated fault tolerance.
Reference: ANSI/TIA-942-C & Uptime Institute Tier Standard: Topology (Tier II vs. Tier III)
A technician decommissions four 2U compute nodes from the middle of a 42U cabinet in a cold-aisle-contained row, leaving an 8U open gap. Why must snap-in blanking panels be installed immediately?
To provide structural shear bracing required to hold the remaining servers on their slide rails.
To block hot rear exhaust from recirculating into cold server intakes.
To increase static air pressure inside the hot aisle so CRAC return fans draw less electrical current.
To satisfy NFPA 70E arc-flash containment rules for low-voltage Ethernet patch cables.
Show the answer
B. To block hot rear exhaust from recirculating into cold server intakes.
Open U-spaces create a low-resistance short circuit allowing hot exhaust air from the rear of the rack to pull straight back into the cold aisle and enter adjacent server intakes, causing localized thermal hotspots and higher server fan power draw. Installing blanking panels seals the front plane.
An enterprise data center is being upgraded from Tier III (Concurrently Maintainable) to Tier IV (Fault Tolerant). Beyond adding a second active power and cooling path, what core architectural requirement distinguishes Tier IV from Tier III?
Installing larger diesel fuel storage tanks rated for at least 96 hours of continuous runtime without refueling.
Automated fault-tolerant failover with physical compartmentalization so an unplanned fault never disrupts IT.
Replacing all dual-corded IT servers with single-corded servers connected through rack static transfer switches.
Operating all UPS modules exclusively in high-efficiency eco-mode during normal utility power conditions.
Show the answer
B. Automated fault-tolerant failover with physical compartmentalization so an unplanned fault never disrupts IT.
Tier IV requires Fault Tolerance: the facility must automatically sustain any single unplanned component failure or distribution-path incident without interrupting critical IT load, and redundant systems must be physically compartmentalized so a localized event (such as a fire or leak) cannot disable both A and B paths simultaneously.
A database server runs a 6-drive RAID 6 array using 4 TB enterprise NVMe drives. Two drives fail over a holiday weekend before a technician arrives. What is the status of the array and its usable capacity?
The array has lost all data because parity arrays can only survive a single drive failure.
The array remains online in degraded mode with 20 TB usable capacity (one parity drive).
Online in degraded mode with 16 TB usable capacity (dual parity).
The array remains online in degraded mode with 12 TB usable capacity (mirrored pairs).
Show the answer
C. Online in degraded mode with 16 TB usable capacity (dual parity).
RAID 6 uses block-level striping with dual independent distributed parity (N - 2 usable capacity). With six 4 TB drives, usable capacity is (6 - 2) × 4 TB = 16 TB, and the array can tolerate up to two simultaneous drive failures while staying online in degraded mode.
Reference: SNIA Common RAID Disk Data Format (DDF) Specification — RAID 6