CDCP, CDCS, DCCA & Cisco CCT Data Center: practice drill
10 realistic exam questions, graded as you go, with the exact rule or statute citation for every answer. Start free, no sign-up.
Timed mock exam
16 questions in 19 minutes, drawn from every topic. No answers shown until the end, then a full score breakdown, your weakest topics and a review of what you missed.
Prices are in US dollars, plus tax where it applies. Stripe, our payment processor, calculates tax at checkout.
All sales are final. If something is really wrong, such as a duplicate charge or a purchase that does not unlock what you bought, write to support@careerexampro.com and we will put it right.
One-time payment. Nothing renews.
You have an exam ticket for this practice test. Start the timed mock exam to use it.
Exam Snapshot & Official Blueprint
Official Exam Fee
$250 (Schneider Electric Energy University / Kryterion)
Format & Time Limit
60 MCQs · 60 minutes (online proctored)
Passing Standard
70% passing score
Typical Prep Incumbents
$250–$600 (Energy University modules + exam)
Official Domain Breakdown
Exam Domain
Weight
Power Architecture, UPS Topologies (Double-Conversion / Eco) & Battery Care
30%
Cooling Fundamentals, Hot/Cold Aisle Containment & PUE Optimization
UPS Topologies: Online double-conversion (VFI) isolates critical load completely from utility sags/surges with 0 ms transfer time; line-interactive regulates voltage via autotransformer with brief transfer.
Airflow Hygiene: Install blanking panels in every empty rack U-space, seal floor grommets, and enforce hot/cold aisle containment to eliminate recirculation and bypass air.
Battery Life Drivers: VRLA battery life halves for every ~8–10°C (15–18°F) rise above 25°C (77°F); lithium-ion offers higher energy density and longer cycle life but requires dedicated BMS and NFPA 855 thermal-runaway controls.
Frequently Asked Questions
Does the Schneider Electric DCCA credential expire?
DCCA is widely recognized across colocation and hyperscale hiring teams as a foundational critical-facilities credential covering power, cooling, racks, and DCIM.
Exact question counts, passing scores, and allowed reference materials vary by testing window and state/agency. Always confirm current rules with the official testing provider.
Sample questions
Under EIA-310-D / IEC 60297 rack standards, what is the vertical height of one rack unit (1U), and where should the heaviest storage JBODs or rack-mount UPS units be installed inside a 42U cabinet?
1.75 in (44.45 mm); mount heaviest chassis at the bottom for stability.
2.00 inches (50.80 mm); mount the heaviest chassis at the top to aid natural convection cooling.
1.50 inches (38.10 mm); mount the heaviest chassis in the middle at 20U–24U for ergonomic access.
1.75 inches (44.45 mm); mount the heaviest chassis at the top so overhead cable trays support them.
Show the answer
A. 1.75 in (44.45 mm); mount heaviest chassis at the bottom for stability.
One standard rack unit (1U) equals 1.75 inches (44.45 mm), containing three mounting holes spaced across the rail. Heavy equipment (UPS modules, battery packs, dense storage enclosures) must always be mounted at the bottom of the rack to lower the center of gravity and prevent tip-over hazards when sliding rails out.
A colocation facility has N+1 redundant UPS modules and chillers, but only a single active chilled-water distribution loop and a single electrical switchgear path serving the computer room. Taking the main switchgear offline for preventive maintenance requires shutting down IT racks. What is the highest Uptime Institute Tier level this design satisfies?
Tier II, because it provides redundant capacity components without concurrent maintainability of distribution paths.
Tier III, because N+1 UPS modules and N+1 chillers are sufficient to achieve concurrent maintainability.
Tier IV, because an N+1 capacity layout automatically isolates any planned electrical switching event.
Tier I, because having N+1 redundant capacity components is ignored unless dual utility substations exist.
Show the answer
A. Tier II, because it provides redundant capacity components without concurrent maintainability of distribution paths.
Uptime Institute Tier II adds redundant capacity components (such as N+1 UPS units and chillers) to a single non-redundant distribution path, meaning planned maintenance on the distribution path still forces an IT shutdown. Tier III requires concurrent maintainability across every component and distribution path, while Tier IV adds automated fault tolerance.
Reference: ANSI/TIA-942-C & Uptime Institute Tier Standard: Topology (Tier II vs. Tier III)
A technician decommissions four 2U compute nodes from the middle of a 42U cabinet in a cold-aisle-contained row, leaving an 8U open gap. Why must snap-in blanking panels be installed immediately?
To provide structural shear bracing required to hold the remaining servers on their slide rails.
To block hot rear exhaust from recirculating into cold server intakes.
To increase static air pressure inside the hot aisle so CRAC return fans draw less electrical current.
To satisfy NFPA 70E arc-flash containment rules for low-voltage Ethernet patch cables.
Show the answer
B. To block hot rear exhaust from recirculating into cold server intakes.
Open U-spaces create a low-resistance short circuit allowing hot exhaust air from the rear of the rack to pull straight back into the cold aisle and enter adjacent server intakes, causing localized thermal hotspots and higher server fan power draw. Installing blanking panels seals the front plane.